A New STATCOM Model for Power Flows Using the Newton–Raphson Method
Enrique Acha, Senior Member, IEEE, and Behzad Kazemtabrizi, Member, IEEE
Abstract—The paper presents a new model of the STATCOM aimed at power ?ow solutions using the Newton–Raphson method. The STATCOM is made up of the series connection of a voltage-source converter (VSC) and its connecting transformer. The VSC is represented in this paper by a complex tap-changing transformer whose primary and secondary windings correspond, notionally speaking, to the VSC’s ac and dc buses, respectively. The magnitude and phase angle of the complex tap changer are said to be the amplitude modulation index and the phase shift that would exist in a PWM inverter to enable either reactive power generation or absorption purely by electronic processing of the voltage and current waveforms within the VSC. The new STATCOM model allows for a comprehensive representation of its ac and dc circuits—this is in contrast to current practice where the STATCOM is represented by an equivalent variable voltage source, which is not amenable to a proper representation of the STATCOM’s dc circuit. One key characteristic of the new VSC model is that no special provisions within a conventional ac power ?ow solution algorithm is required to represent the dc circuit, since the complex tap-changing transformer of the VSC gives rise to the customary ac circuit and a notional dc circuit. The latter includes the dc capacitor, which in steady-state draws no current, and a current-dependent conductance to represent switching losses. The ensuing STATCOM model possesses unparalleled control capabilities in the operational parameters of both the ac and dc sides of the converter. The prowess of the new STATCOM power ?ow model is demonstrated by numerical examples where the quadratic convergence characteristics of the Newton–Raphson method are preserved. Index Terms—FACTS, Newton–Raphson method, power ?ows, STATCOM, voltage source converter (VSC).

I. INTRODUCTION

T

HE STATCOM is a key element of the FACTS technology. It is the modern counterpart of the well-established Static Var Compensator (SVC) and forms the basic building block with which other more advanced FACTS equipment may be built, such as the UPFC and the various forms of VSC-HVDC links. Indeed, the latter application has blurred the line between the FACTS and HVDC transmission options. In its most basic form, the STATCOM may be seen to comprise a voltage source converter (VSC) and a connecting transformer

Manuscript received March 29, 2012; revised July 12, 2012 and November 21, 2012; accepted December 27, 2012. Date of publication January 23, 2013; date of current version July 18, 2013. Paper no. TPWRS-00312-2012. E. Acha is with the Department of Electrical Energy Engineering, Tampere University of Technology, Tampere 33101, Finland (e-mail: enrique.acha@tut.?). B. Kazemtabrizi is with the School of Engineering and Computer Science, University of Durham, Durham DH1 3HP, U.K. (e-mail: behzad.kazemtabrizi@durham.ac.uk). Digital Object Identi?er 10.1109/TPWRS.2012.2237186

which, more often than not, is a load tap-changing (LTC) transformer [1], [2]. Current models aimed at fundamental frequency studies have it represented as a controllable voltage source behind a coupling impedance, very much in the same vein as the model of a synchronous condenser [2], [3]. This simple concept represents well the fact that, at the fundamental frequency, the STATCOM converter’s output voltage may be adjusted against the ac system’s voltage to achieve very tight control targets, a capability afforded by the switched-mode converter technology [1]–[8]. By way of example, the reactive power ?ow may be controlled by adjusting the converter’s output voltage magnitude against the ac system voltage [1], [2]. The controllable voltage source concept explains the STATCOM’s steady-state operation from the vantage of its ac side. However, it fails to explain its operation from the dc side. A notable exception is the equivalent voltage source model reported in [9], where the STATCOM’s ac voltage is expressed as a function of the dc voltage and the amplitude modulation ratio. Nevertheless, incorporation of the switching losses in the dc bus or a dc load would be dif?cult to represent in this model owing to its equivalent voltage source nature. In most STATCOM models aimed at fundamental frequency power ?ows, there is no easy way to ascertaining whether or not the converter’s operation is within the linear region of operation [10]. Also, the switching losses tend to be neglected, and the ohmic losses of the converter, along with the effects of the converter’s magnetics, are normally lumped together with those of the interfacing transformer. To circumvent these shortcomings, a new STATCOM model is put forward in this paper where the VSC is represented by a tap-changing transformer and a variable shunt susceptance. The primary and secondary sides of this tap-changing transformer may be interpreted as the VSC’s ac and dc sides, respectively. Such a VSC model takes into account, in an aggregated form, the phase shifting and scaling nature of the PWM control. That is, its magnitude and phase angle are assigned to be the amplitude modulation index and the phase shift that would exist in a PWM inverter to enable either reactive power generation or absorption purely by electronic processing of the voltage and current waveforms within the VSC. It should be noted that the VSC is designed to operate on a constant dc voltage and that a relatively small capacitor is used to support and stabilize the voltage at its dc bus. Moreover, this small rating capacitor does not contribute per se to the reactive power exchange with the power grid [11]. The new model takes due account of the VSC switching and ohmic losses separately. It should be noted that in the new VSC model no special provisions within a conventional ac power ?ow solution algorithm is required to represent the dc circuit. The reason is that the complex tap-changing transformer of the VSC yields the customary ac circuit and a notional dc

0885-8950/$31.00 ? 2013 IEEE

2456

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 3, AUGUST 2013

circuit. The VSC model is series-connected with the LTC transformer model to make up the new STATCOM representation; a model with enhanced control capabilities in the operational parameters of both the ac and dc sides of the converter. Such control modelling ?exibility attains special relevance when applied to the realm of VSC-HVDC or UPFC but these subject matters are topics of forthcoming publications. It should be pointed out that the concept of a complex ideal transformer to model a VSC has been applied elsewhere in connection with the UPFC [12], [13]. However, its shunt-connected VSC is represented by a variable susceptance and it is only its series-connected VSC that is represented by a complex ideal transformer-such an approach represents only an approximation to the conventional two-voltage source model of the UPFC [14], [15]. More importantly, both UPFC models, that reported in [12], [13] and that reported in [14], [15], lack dc bus representation. II. NEW VSC MODEL A. VSC Main Characteristics The STATCOM comprises the series connection of a VSC and an LTC transformer whose primary winding is shunt-connected with the ac power network. Physically, the VSC is built as a two-level or a multilevel inverter that uses a converter bridge made up of self-commutating switches driven by PWM control. It uses a small capacitor bank on its dc side to support and stabilize the dc voltage to enable converter operation. The converter keeps the capacitor charged to the required voltage level by making its output voltage lag the ac system voltage by a small phase angle [1]. The dc capacitor bank of value is shown schematically in Fig. 1(a). It should be stated that is not used per se in the VAR generation/absorption process. Instead, this process is carried out by action of the PWM control which shifts the voltage and current waveforms within the VSC to yield either leading or lagging VAR operation to satisfy operational requirements. It is said that the VSC has no inertia, its response is practically instantaneous, it does not signi?cantly alter the existing system impedance and it can internally generate reactive (both capacitive and inductive) power [11]. For the purpose of fundamental frequency analysis, the VSC’s electronic processing of the voltage and current waveforms is well synthesized by the notional variable susceptance, , which connects to the ac bus of the ideal complex tap-changing transformer—see Fig. 1(b). Note that is responsible for the whole of the reactive power production in the valve set of the VSC. B. VSC Nodal Admittance Matrix Representation The fundamental frequency operation of the VSC shown schematically in Fig. 1(a) may be modeled by means of electric circuit components, as shown in Fig. 1(b). From the conceptual point of view, the central component of this VSC model is the ideal tap-changing transformer with complex tap which, in the absence of switching losses, may be seen to act as a nullator that constrains the source current to zero, with the source being the capacitor , and the associated norator being the variable susceptance [17]. Indeed, in steady-state operation the dc capacitor may be represented as a battery that yields voltage and draws no current [18]—this point is addressed in more detail in Appendix A. Notice that the

Fig. 1. (a) VSC schematic representation. (b) VSC equivalent circuit.

winding connected to node 1 is an ac node internal to the VSC and that the winding connected to node 0 is a notional dc node. Two elements connect to the VSC’s dc bus, namely, the source and the current-dependent resistor . Hence, the ideal tap-changing transformer is the element that provides the interface for the VSC’s ac and dc circuits, as illustrated in Fig. 1(b). It should be emphasized that no reactive power ?ows through it, only real power which is akin to dc power. We have drawn our inspiration to develop this model, from the following basic relationship: (1) of the ideal tap-changing transwhere the tap magnitude former corresponds to the VSC’s amplitude modulation coef?cient where the following relationship holds for a two-level, three-phase VSC: , where, in the linear range of modulation, the amplitude modulation index takes values within bounds: [19]. The phase angle is the phase angle of the complex voltage relative to the system phase reference, and is the dc bus voltage which is a real scalar and on a per-unit basis carries a value of . Other elements of the electric circuit shown in Fig. 1(b) are the series impedance which is connected to the ideal transformer’s ac side. The series reactance represents the VSC’s interface magnetics. The series resistor accounts for the ohmic losses which are proportional to the ac terminal current squared. Note that the secondary winding current , which is always a real quantity, splits into and . The latter current is always zero during steady-state operation. This is further elaborated in Appendix A, where the role of the VSC’s phase-shifting transformer is analyzed from the vantage of electronic circuits [17]. As one would expect, the complex power conservation property of the ideal transformer in Fig. 1(b) stands but note that

ACHA AND KAZEMTABRIZI: NEW STATCOM MODEL FOR POWER FLOWS USING THE NEWTON–RAPHSON METHOD

2457

there is no reactive power ?owing through it, since all the reactive power requirements of the VSC model (generation/absorption) are met by the shunt branch connected at node 1. The power relationships between nodes 1 and 0, which account for the full VSC model, are

and more explicitly

(8) Notice that this expression represents the VSC equivalent circuit in Fig. 1(b) in steady-state, with the capacitor effect represented by the dc voltage . C. VSC Nodal Power Equations The complex power model is derived from the nodal admittance matrix, given by (9), shown at the bottom of the page, where, subsequently, the dc voltage will be referred only as as opposed to . Following some arduous algebra, the nodal active and reactive power expressions are arrived at

(2) The switching loss model corresponds to a constant resistance (conductance) , which under the presence of constant dc voltage and constant load current, would yield constant power loss for a given switching frequency of the PWM converter. Admittedly, the constant resistance characteristic may be inaccurate because although the dc voltage is kept largely constant, the load current will vary according to the prevailing operating condition. Hence, it is proposed that the resistance characteristic derived at rated voltage and current be corrected by the quadratic ratio of the actual current to the nominal current (3) would be a resistive term exhibiting a degree of where power behavior. The voltage and current relationships in the ideal tap-changing transformer are (4) The current through the admittance connected between nodes and 1 is (5) . where At node 0, the following relationship holds:

(10) D. VSC Linearized System of Equations These equations are nonlinear and their solution, for a prede?ned set of generation and load pattern may be carried out using the Newton–Raphson method. This involves repeated linearization of the nodal power equations. Their initial evaluation requires an informed guess of the state variable values: , when the aim is to regulate voltage magnitude at bus using the VSC’s amplitude modulation ratio and keep at a constant value. In practice, the latter is possible due to the dc capacitor’s action. The linearized system of equations is given by (11), shown at the bottom of the following page. Subsequent evaluations of the nodal power equations are carried out using the improved set of values being furnished by the iterative process: , where is the iteration counter. In this application, the regulated powers and also form part of the control set. The entries making up (11) are given in Appendix B.

(6) Combining (5) and (6) and incorporating constraints from the electric circuit in Fig. 1(b), we obtain

(7)

(9)

2458

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 3, AUGUST 2013

1) Mismatch Power Terms and Control Variables: A mismatch power term is the difference between the net power and the calculated power at a given bus, say , and 0. The calculated powers are determined using the nodal power (10), giving

voltage magnitude is regulated within system-dependent maximum and minimum values, afforded by the following basic relationship: (14) Note that, in the VSC’s linear range of modulation, the index takes values within the bounds: and that . However, in power systems reactive power control applications, it is unlikely that values of lower than 0.5 will be used. The reason is that voltage magnitude at the VSC’s ac bus must be kept within practical limits because too high a voltage may induce insulation coordination failure at the point of connection with the power grid and too low a voltage may induce a condition of voltage collapse. Note that with realistic values of 0.001 p.u., 0.01 p.u. and 2 p.u. and considering low-current operation, say 0.1 p.u., will take a value of 0.6114 p.u. with . In the power ?ow solution, the active and reactive powers are regulated on the VSC’s dc bus—the former is set to either zero or to a speci?ed dc load, whereas the latter is always set to zero. b) Simplifying Assumptions: A key feature of this model is that the phase angle value at node 0 is independent of circuit parameters or network complexity to the left of the phase-shifting transformer. The reason is that the ideal phase shifter decouples, angle-wise, the circuits to the left and to the right of the ideal transformer. Moreover, the phase angle voltage at bus 0 keeps its value given at the point of initialization. Hence, in the application pursued in this paper, it makes sense to stick to zero phase angle voltage initialization for this bus—when looked at it from the vantage of rectangular coordinates, its imaginary part does not exist. This may reduce the linearized equation (11) by one row and one column since the value of is known a priori, i.e., . c) Initial Parameters and Limits: Three VSC parameters require initialization. They are the amplitude modulation ratio and its phase angle . They are normally set at and 0, respectively. The VSC is assumed to operate within the linear region, whereas the phase angle is assumed to have no limits. The third parameter is the equivalent shunt susceptance , wich is given an initial value that lies within the range and . E. VSC Test Cases The VSC model is applied in a rather contrived test case where the STATCOM is connected at the receiving end of a loaded transmission line to illustrate its performance, and for

(12) The mismatch power ?ow in branch is the difference between the target power ?ow at the branch and the calculated power. In the VSC application, both active and reactive power targets are normally set to zero. 2) State Variables and Increments: The state variable increments calculated at iteration with the power ?ow model are

(13) 3) Nonregulated Solutions: If no voltage regulation at node is applied, the voltage magnitude replaces as state variable in the linearized power ?ow equation (11). Other control options may be available, but some caution needs to be exercised in the VSC and STATCOM applications because power regulation at node cannot be achieved since the internal power losses are not known a priori, and voltage control in the dc node 0 is achieved by virtue of the dc capacitor. 4) Practical Implementations: a) Control Strategy: As illustrated in Fig. 1(b), the VSC is assumed to be connected between a sending bus and a receiving bus 0, with the former taken to be the VSC’s ac bus and the latter taken to be the VSC’s dc bus. The voltage is kept constant by the action of a small dc capacitor bank with rated capacitance , which in steady-state draws no current. In the Newton–Raphson power ?ow solution the dc bus will be treated as a -type node with zero nodal power injection and a constant voltage magnitude of value . Likewise, the

(11)

ACHA AND KAZEMTABRIZI: NEW STATCOM MODEL FOR POWER FLOWS USING THE NEWTON–RAPHSON METHOD

2459

Fig. 2. VSC providing voltage support at bus 2.

Fig. 3. Test circuit using the conventional voltage source representation of the VSC.

TABLE I POWER FLOW SOLUTION FOR VARIOUS PHASE ANGLES AT THE SLACK BUS

ease of reproduction. At this point in the paper, it is assumed that the STATCOM transformer is a conventional transformer and that its leakage reactance is lumped together with the reactance of the VSC. Hence, we shall refer to it as VSC as opposed to STATCOM. Three cases are considered: 1) the VSC is used to provide reactive power; 2) the VSC is used to draw reactive power; and 3) the VSC is used to supply a dc load. a) Test Case 1: The three-node system shown in Fig. 2 comprises one generator, one transmission line and one ac/dc converter (VSC), which is represented by the elements shown within the broken-line rectangle. The generator node is taken to be the Slack bus where the voltage magnitude is kept at 1 p.u. and its phase angle provides a reference for all other phase angles in the network, excepting bus 0, where the phase angle is always zero in the STATCOM or VSC application. Bus 0 would be interpreted as the dc bus of the VSC circuit where the voltage is always a real quantity. The following parameters are used in this system: 1) transmission line resistance and reactance: 0.05 p.u. and 0.10 p.u.; 2) VSC series resistance and reactance: 0.01 p.u., 0.10 p.u.; 3) VSC nominal values of shunt conductance and susceptance: 0.01 and 1.05 p.u.; 4) active and reactive power load at node 2: 0.25 p.u. and 0.20 p.u. As already stated in Section II-D(b), the phase angle value at node 0 is independent of circuit parameters, network complexity and initializing conditions left of the phase shifter transformer—it is not speci?c to this circuit under test. To prove this point, different initial values are given to the Slack bus and the resulting voltages shown in Table I. It should be noted that the phase angle voltage at bus 0 keeps its value given at the point of initialization and that in the application pursued in this paper, we shall stick to zero phase angle voltage initialization for this bus. When looked at it from the vantage of rectangular coordinates, its imaginary part does not exist. Indeed, an equivalent solution would be obtained by using a linearized equation akin to (11) but with no provision for the state variable .

The phase angle difference between buses 1 and 2 is, in each case: . The Newton–Raphson power ?ow algorithm converges in seven iterations in all three cases, to a mismatch tolerance of . The symbol is used in this table to signify “akin to.” The VSC consumes 0.0271 p.u. of active power from the system to account for its internal losses whilst supplying 0.8817 p.u. of reactive power to the system. The equivalent susceptance (in capacitive mode) produces 0.9523 p.u. of reactive power and its capacitive susceptance stands at 0.7408 p.u. As one would expect, the VSC switching losses are 2%, corresponding to a conductance . The dc bus voltage is controlled at 1.4142 p.u. and the voltage magnitude at bus 2 is kept at 1.05 with a “true” . Notice that . The phase shifter angle takes a value of . The line current drawn by the VSC is . For the sake of completeness, the test case is solved by modeling the VSC using its well-known representation based on the equivalent voltage source [1]–[4], which, in this case, has been extended to incorporate a shunt resistor to account for the VSC’s switching losses. Note that all the relevant parameters for this circuit are the same as in the circuit in Fig. 2, except that the resistance corresponding to the switching losses is connected on the left-hand side of the complex tap changer and, accordingly, it is affected by the square of the “off-nominal turns ratio” , i.e., . Node 0 is treated as a -type bus with zero active power injection and its voltage magnitude corresponds to the dc-like voltage of 1.4142 p.u. in the circuit of Fig. 2, affected by , i.e., . The results were obtained using a conventional power ?ow program where bus 0 is treated as a PV bus with zero active power contribution and set to regulate voltage magnitude at the bus at 1.1338 p.u. As expected, the iterative solutions furnished by both modeling approaches yield similar results but the results at bus 0 merit additional analysis.The complex voltage at the equivalent voltage source corresponds to the cascading of the voltage at bus 0 in Fig. 2 and its phase shifter complex tap value. Furthermore, the reactive power contributed by the equivalent susceptance in the test circuit of Fig. 2 equals the reactive power generated by the equivalent voltage source in the test circuit of Fig. 3. The following limitations spring to mind in the voltage source model of the VSC compared to the new model introduced in this paper: 1) the voltage magnitude of the voltage source is dif?cult to determine since only the dc voltage is known and the amplitude modulation index is not known a priori and 2) by the same token, the switching losses will only be known approximately.

2460

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 3, AUGUST 2013

Fig. 4. Test network uses the same circuit parameters as in Test Case 1 but the to force the reactive voltage magnitude at bus 2 is kept at 0.95 p.u. using power ?ow into the VSC.

Fig. 5. Test network with a battery load on its dc bus.

In this numerical example, the switching loss correction given by (3) was not applied in order to be able to compare the response furnished by the two VSC models, namely, the new VSC model and the equivalent voltage source model. In any case, little change is expected since the current magnitude (0.8402 p.u.) is close to the 1-.u. rated current. Perhaps the most noticeable change is a reduction in the switching loss from 2% to 1.4% and the ensuing adjustment in active power ?ows. b) Test Case 2: The operating conditions of the power circuit in Test Case 1 are modi?ed to force the VSC to draw reactive power from the slack generator connected at bus 1. As shown in Fig. 4, the nodal voltage magnitude at node 2 (0.95 p.u.) is kept at a lower voltage magnitude than the voltage at node 1 (1 p.u.). The VSC draws 0.0007 p.u. of active power and 0.1493 p.u. of reactive power. The equivalent susceptance absorbs 0.1469 p.u. of reactive power and its inductive susceptance stands at 0.1682 p.u. The VSC switching losses are low, 0.05%, since the current drawn by the VSC is quite small, i.e. . The dc bus voltage is controlled at 1.4142 p.u. and the voltage magnitude at bus 2 is kept at 0.95 with . The phase shifter angle takes a value of . c) Test Case 3: Test Case 1 is expanded to incorporate a load in the dc side of the VSC in the form of a battery system, as shown in Fig. 5. This test network uses the same circuit parameters as in Test Case 1, but a second load is added in the form of a battery which is being supplied through the VSC at 0.5 p.u. of power. The VSC is used to keep the voltage magnitude at 1.05 p.u. at bus 2. The total VSC active power loss stands at 4.76% p.u. where 3.18% corresponds to switching loss and 1.58% corresponds to ohmic loss. The VSC contributes 1.2046 p.u. to supply the reactive power load of 0.20 p.u. and the rest being exported to the Slack generator. The VSC equivalent susceptance with a capacitive value of 1.0111 p.u. produces 1.3634 p.u. of reactive power. The SVC is set to regulate voltage magnitude at its ac bus at 1.05 p.u. and its actual complex modulation ratio is: . The current drawn by the VSC is

Fig. 6. LTC transformer equivalent.

. The solution converges in 7 iterations to a tolerance of . III. POWER FLOW STATCOM MODEL For studies at the fundamental frequency, the STATCOM may be seen to comprise a VSC and an interfacing transformer, which may be a load tap changer (LTC). The VSC schematic representation and equivalent circuit are given in Fig. 1 and the equivalent circuit of the LTC transformer is given in Fig. 6. Inclusion of the STATCOM model in a power ?ow solution is straightforward. It only requires explicit representation of the nodal power ?ow equations of the VSC connected between say, nodes 0 and , and the nodal power equations of the LTC transformer connected between say, nodes and . Alternatively, a more compact set of power ?ow equations may be achieved by realizing that the interface point between the VSC and LTC circuits, namely node, receives a zero external (nodal) current injection. Then a mathematical elimination of node becomes an option. However, it should be noted that this reduced model is only attractive if we are prepared to lose a degree of modeling ?exibility, since this bus is not explicitly available for regulating action of either or . Instead, the combined regulating action will take place in the high-voltage side of the LTC transformer. A. Reduced STATCOM Nodal Admittance Matrix The nodal admittance matrix of the LTC transformer in Fig. 6 is (15) Combining the two individual models yields the compound model representing the VSC-LTC or STATCOM model given by (16), shown at the bottom of the page.

(16)

ACHA AND KAZEMTABRIZI: NEW STATCOM MODEL FOR POWER FLOWS USING THE NEWTON–RAPHSON METHOD

2461

Mathematical elimination of node yields the reduced nodal admittance matrix given by (17), shown at the bottom of the page, where and . B. STATCOM Nodal Power Equations Following a similar procedure as in Section II-C for the derivation of the nodal power equations of the VSC, the active and reactive power expressions for the STATCOM model are derived as

(18) where

The numerical solution of equation system equation (18), for a pre-de?ned set of generation and load pattern, is carried out very ef?ciently by iteration using the Newton–Raphson method. Similarly to the VSC model in Section II-C, this involves repeated linearization of the nodal power equations and their initial evaluation requires an informed guess of the state variables values: . The linearized system

of equations may be compacted further by eliminating the row and column associated to the variable , since this is known a priori variable that keeps its value at the point of initialization, which in this application is zero. The ensuing equation is given by (19), shown at the bottom of the following page, where is used to signify the use of either or . The attraction of (19) is its rather compact nature in representing the combined operation of the VSC and the LTC transformer with only four variables. However, this comes at a price—some modeling ?exibility is lost. Notice that, since the connecting bus between the VSC and the LTC is not explicitly available in this combined model, it cannot be controlled by the regulating action of either or . Also, since the dc bus is regulated by the action of the dc capacitor and treated in the power ?ow solution as a bus then and are available solely for the purpose of regulating voltage magnitude at the high-voltage bus of the LTC transformer. Hence, the regulating action of and is sequential in this model. It should be emphasized that, from the power ?ow solution vantage, there is no actual restriction in attempting to control the dc bus voltage with either or . However, from the equipment operation point of view, this regulating action is hardly ever done. Subsequent evaluations of the nodal power equations are carried out using the improved set of values furnished by the iterative process: , where is the iteration counter. It should be noticed that in this formulation, the control capabilities have been extended compared to that of the VSC in (11). It becomes possible to regulate nodal voltage magnitude at the STATCOM terminal (bus ) using the combined action of the LTC tap and the VSC amplitude modulation coef?cient , one at the time. It should be remarked that in an actual VSC, takes continuous values and that in an actual LTC transformer, the tap takes discrete values. Nevertheless, for the purpose of the power ?ow model using the Newton–Raphson method and aiming at maintaining the quadratic convergence characteristic of this iterative algorithm, the variable is assumed to take continuous values. It is at the end of the iterative solution that the tap is moved to the nearest physical tap value and then nodal voltages are re-adjusted and power ?ows and power losses calculated. The mismatch power terms and control variables remain the same as in (12), except that the subscript replaces the subscript . In the state variables increments in (13), the subscript is also replaced by the subscript and the newly introduced state variable replaces as

(20) and where respectively. are normally initialized at 1 and ,

(17)

2462

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 3, AUGUST 2013

Fig. 7. Upgraded network used in Test Case 1 to include the LTC transformer.

C. STATCOM Test Cases Two test cases are presented here to illustrate the control ?exibility afforded by the reduced STATCOM model. The ?rst case relates to a contrived system which is, essentially, the same system as that used in Test Case 1, except that the STATCOM model replaces the VSC model. The second test case is a modi?ed version of the IEEE 30-node system [16] where two STATCOMs regulate voltage magnitude at two different points in the network. a) Test Case 4: The power circuit in Test Case 1 is modi?ed to replace the VSC connected at bus 2 by a STATCOM, where the LTC’s STATCOM ?gures prominently in Fig. 7. The test network uses the same circuit parameters as in Test Case 1 except that the parameters of the LTC transformer are added to the circuit parameters: 0.01 p.u. and 0.10 p.u. The tap limits are: . The generator keeps the voltage magnitude at the slack node at 1 p.u. The STATCOM consumes 0.0304 p.u. of active power from the system to account for its internal losses whilst supplying 0.8836 p.u. of reactive power to the system. The VSC switching losses stand at and the remaining 1.62% correspond to ohmic losses in the LTC transformer and VSC. The dc bus voltage is kept at 1.4142 p.u. by action of the dc capacitor and this bus is treated in the power ?ow solution as a bus. The voltage magnitude at bus 2 is kept at 1.05 p.u. with a combination of a selected of 0.8945 and a resulting transformer tap of . The current drawn by the STATCOM is . b) Test Case 5: In order to test the performance of the proposed STATCOM model in a larger power network, the IEEE 30-node system is selected [16]. The ?x banks of capacitors at nodes 10 and 24 in the original network are replaced with STATCOMs which are set to regulate voltage magnitudes at

Fig. 8. STATCOMs supplying reactive power at buses 10 and 24 of the modi?ed IEEE 30-bus system.

TABLE II VOLTAGE MAGNITUDES AT THE COMPENSATED BUSES IN THE 30-BUS SYSTEM FOR TWO COMPENSATION OPTIONS

their points of connection with the power grid. Their respective dc voltages are kept at 1.4142 p.u. The relevant portions of the modi?ed 30-bus system are shown in Fig. 8. The voltage magnitudes at the compensated buses, namely, 10 and 24, are compared in Table II to the case when conventional capacitor banks are connected to these nodes, and when no compensation is used.

(19)

ACHA AND KAZEMTABRIZI: NEW STATCOM MODEL FOR POWER FLOWS USING THE NEWTON–RAPHSON METHOD

2463

TABLE III POWER LOSS AT THE COMPENSATED BUSES IN THE 30-BUS SYSTEM FOR TWO COMPENSATION OPTIONS

The power ?ow solutions converged in 6 iterations for the ?rst two cases and . in seven iterations for the STATCOMs, to mismatch a tolerance of

Fig. 9. Equivalent circuit showing the ideal phase-shifting transformer of . Fig. 1(b) and neighboring elements, where

The two STATCOMs use identical parameters and their LTC transformers are set at their nominal tap positions . They are assumed to contain no resistance and their reactances are . The VSCs series and shunt parameters, in per-unit, are: , , , and , respectively. The susceptance values used for the case with ?x compensation at buses 10 and 24 are 0.19 and 0.043 p.u., which are the values given in [16]. For the STATCOM case, the voltages at buses 10 and 24 are kept at the same level as those given by the case with ?x compensation. As expected, one bene?t of shunt compensation is to reduce the system power losses due to an improved voltage pro?le, and this trend is shown in the power loss ?gures presented in Table III. The STATCOM-type compensation introduces an additional kind of power loss which is associated with the high-frequency switching of the PWM control used by the VSC technology and ohmic losses. The STATCOM losses are quite low in this case because the currents drawn by the two STATCOMs are low compared to the 1 p.u. rated currents namely, and . IV. CONCLUSION A new STATCOM model aimed at power ?ow solutions using the Newton–Raphson method has been introduced. The model represents a paradigm shift in the way the fundamental frequency, positive sequence VSC-FACTS controllers are represented. It does not treat the controller as an idealized controllable voltage source but rather as a compound transformer device to which certain control properties of PWM-based inverters may be linked. This argument is similar to the one advanced for dc-to-dc converters which have been linked, conceptually speaking, to step-up and step-down transformers [19]. The phase angle of the complex tap changer represents the phase shift that would exist in a PWM inverter and coincides with the phase angle of the conventional voltage source model of the VSC. More speci?cally, this would be the phase angle required by the VSC to enable either reactive power generation or absorption purely by electronic processing of the voltage and current waveforms within the VSC. The switching losses, ohmic losses and the connecting LTC transformer are all explicitly represented in the new STATCOM model. The complex tap changer in the VSC model and the real tap changer in the LTC model enable an effective voltage regulation at the point of connection with the grid and at the VSC’s ac node. The model has been tested in a simple system for ease of reproduction by interested parties. A larger power system has also been used to show that the new STATCOM power ?ow model retains its strong convergence characteristics.

APPENDIX A IDEAL PHASE-SHIFTER CIRCUIT One salient characteristic of the new VSC model is that no special provisions within a conventional ac power ?ow solution algorithm is required to represent the dc circuit, since the complex tap-changing transformer of the VSC may be used with ease to give rise to the customary ac circuit and a notional dc circuit. However, some further explanation is required since the modelling development involves the con?ation of ac and dc circuit concepts at an equivalent node, brought about by the use of the ideal tap-changing transformer concept. In order to elaborate the explanation from the vantage of electronic circuits, we are going to assume that the conductance associated with switching losses, , in Fig. 1(b), may be referred to the primary side of the ideal transformer. The relevant part of the circuit illustrating such a situation but with capacitor representation, as opposed to its equivalent battery representation, is shown in Fig. 9, By invoking (4), we obtain (A1) (A2) In steady-state, a charged dc capacitor draws zero current and it is well-accepted that it may be represented as a charged battery [18] and, by extension, as a dc voltage source feeding no current. These facts are re?ected by (A1) and (A2) and give the opportunity to interpret the circuit in Fig. 9 in terms of electronic circuits concepts. Hence, it may be argued that in steady-state this circuit behaves as a nullor operating on a dc source representing the dc capacitor. The nullor is made up of a nullator and a norator [17], represented in this case by the ideal phase-shifting transformer and the equivalent admittance, , respectively. The circuit in Fig. 9 may be redrawn as in Fig. 10. The nullator and the norator are said to be linear, time-invariant one-port elements. The former is de?ned as having zero current through it and zero voltage across it. The latter, on the other hand, can have an arbitrary current through it and an arbitrary voltage across its terminals. Nullators have properties of both short-circuit (zero voltage) and open-circuit (zero current) connections. They are current and voltage sources at the same time. A norator is a voltage or current source with in?nite gain. It takes whatever current and voltage is required by the external circuit to meet Kirchhoff’s circuit laws. A norator is always paired with a nulator [17].

2464

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 3, AUGUST 2013

(B13) (B14) (B15) (B16)
Fig. 10. Interpretation of the equivalent circuit of Fig. 9 in terms of electronic circuit elements.

(B17) (B18)

Either, by careful examination of (A1) and (A2) or by analysis of the electronic equivalent circuit in Fig. 10, it can be seen that the ideal, complex tap-changing transformer of the VSC gives raise to the customary ac circuit and a notional dc circuit where the dc capacitor yields voltage but draws no current. In a more general sense and from the viewpoint of the ac power ?ow solution, if resistive elements or dc power loads are connected to the notional dc bus then currents do pass through the ideal phase-shifting transformer but it would be a component of current that yields a nodal voltage with zero phase angle and, as one would expect, yields power with no imaginary component, hence, no reactive power exists in this part of the notional dc circuit. APPENDIX B PARTIAL DERIVATIVE TERMS FOR THE VSC The partial derivative terms making up the Jacobian matrix in (11) are given below. Note that these derivative terms do not include the current dependency in the switching loss term —refer to (3): (B1) (B2) (B3) (B4) (B5) REFERENCES (B6) (B7) (B8) (B9) (B10) (B11) (B12) ACKNOWLEDGMENT

(B19) (B20)

(B21)

(B22)

(B23)

(B24) (B25)

The authors would like to thank the referees of this paper for the most valuable and insightful criticisms which have enhanced the theoretical basis on which this STATCOM model has been developed.

[1] G. N. Hingorani and L. Gyugyi, Understanding FACTS: Concepts and Technologies of Flexible AC Transmission Systems. New York: IEEE, 2000. [2] E. Acha, C. R. Fuerte-Esquivel, H. Ambriz-Perez, and C. Angeles-Camacho, FACTS Modeling and Simulation in Power Networks. New York: Wiley, 2005. [3] D. J. Gotham and G. T. Heydt, “Power ?ow control and power ?ow studies for systems with FACTS devices,” IEEE Trans. Power Syst., vol. 13, no. 1, pp. 60–65, Feb. 1998. [4] X. Zhang and E. J. Handschin, “Optimal power ?ow control by converter based FACTS controllers,” presented at the 7th Int. Conf. AC-DC Power Transmission, Nov. 28–30, 2001, pp. 250–255. [5] D. M. Brod and D. M. Novotny, “Current control of VSI-PWM inverters,” IEEE Trans. Ind. Appl., vol. IA-21, no. 4, pp. 562–570, Aug. 1985. [6] H. W. van der Broeck, H. C. Skudelny, and G. V. Stanke, “Analysis and realisation of pulsewidth modulator based on voltage space vectors,” IEEE Trans. Ind. Appl., vol. 24, no. 1, pp. 142–150, Feb. 1988.

ACHA AND KAZEMTABRIZI: NEW STATCOM MODEL FOR POWER FLOWS USING THE NEWTON–RAPHSON METHOD

2465

[7] R. Wu, S. B. Dewan, and G. R. Slemon, “A PWM AC-to-DC converter with ?xed switching frequency,” IEEE Trans. Ind. Appl., vol. 26, no. 5, pp. 880–885, Oct. 1990. [8] R. Wu, S. B. Dewan, and G. R. Slemon, “Analysis of an PWM AC-to-DC voltage source converter using PWM with phase and amplitude control,” IEEE Trans. Ind. Appl., vol. 27, no. 2, pp. 355–364, Apr. 1991. [9] C. A. Ca?izares, “Power ?ow and transient stability models of FACTS controllers for voltage and angle stability studies,” in IEEE PES WM, Singapore, Jan. 23–27, 2000, pp. 1447–1454. [10] C. Angeles-Camacho, O. L. Tortelli, E. Acha, and C. R. Fuerte-Esquivel, “Inclusion of a high voltage dc-voltage source converter model in a Newton-Raphson power ?ow algorithm,” Proc. Inst. Electr. Eng. —Gen., Trans. and Dist., vol. 150, pp. 691–696, Nov. 2003. [11] L. Gyugyi, “Dynamic compensation of AC transmission lines by solidstate synchronous voltage sources,” IEEE Trans. Power Del., vol. 9, no. 2, pp. 904–911, Apr. 1994. [12] S. An and T. W. Gedra, “UPFC ideal transformer model,” in Proc. North Amer. Power Symp., Oct. 2003, pp. 46–50. [13] S. An, J. Condren, and T. W. Gedra, “An ideal transformer model, OPF ?rst-order sensitivities, and application to screening for optimal UPFC locations,” IEEE Trans. Power Syst., vol. 22, no. 1, pp. 68–75, Feb. 2007. [14] C. R. Fuerte-Esquivel, E. Acha, and H. Ambriz-Perez, “A comprehensive Newton-Raphson UPFC model for the quadratic power ?ow solution of practical power networks,” IEEE Trans. Power Syst., vol. 15, no. 1, pp. 102–109, Feb. 2000. [15] H. Ambriz-Perez, E. Acha, C. R. Fuerte-Esquivel, and A. de la Torre, “Incorporation of a UPFC model in an optimal power ?ow using Newton’s method,” Proc. Inst. Electr. Eng.—Gen., Trans. and Dist., vol. 145, no. 3, pp. 336–344, May 1998. [16] IEEE 30-Node Test System [Online]. Available: http://www.ee.washington.edu/research/pstca

[17] C. J. M. Verhoeven, A. van Staveren, G. L. E. Monna, M. H. L. Kouwenhoven, and E. Yildiz, Structured Electronic Design: Negative Feedback Ampli?ers. Norwell, MA: Kluwer, 2003. [18] J. W. Nilsson and S. Riedel, Electric Circuits, 9th ed. Upper Saddle River, NJ: Prentice-Hall, 2010. [19] N. Mohan, T. M. Undeland, and W. P. Robins, Power Electronics: Converters, Applications and Design. New York: Wiley, 2003. Enrique Acha (SM’02) was born in Mexico. He graduated from Universidad Michoacana in 1979 and received the Ph.D. degree from the University of Canterbury, Christchurch, New Zealand, in 1988. He was the Professor of Electrical Power Systems with the University of Glasgow, Glasgow, U.K., from 2001 to 2011, and he is now a Professor of Electrical Power Systems with the Tampere University of Technology, Tampere, Finland. Prof. Acha is an IEEE Power and Energy Society Distinguished Lecturer.

Behzad Kazemtabrizi (S’07–M’12) was born in Tehran, Iran. He received the B.Sc. degree in electrical power engineering from Azad University, Tehran, Iran, in 2006, and the M.Sc. and Ph.D. degrees in electronics and electrical engineering from the University of Glasgow, Glasgow, U.K., in 2007 and 2011, respectively. He is now with the School of Engineering and Computer Science, Durham University, Durham, U.K., as a Research Associate.


相关文章:
链式STATCOM并网LCL滤波器参数的优化设计.pdf
Power System Protection and Control 电力系统保护与...model of STATCOM under the topology of cascaded ...A new method of linear optimization about ...
DYNAMIC PERFORMANCE OF STATCOM UNDER LINE TO_图文.pdf
STATCOM the network by redistributing the line flows and regulating the bus...power system simulation model with 48 pulses implemented VSC based ±100 ...
A STATCOM Model for Optimal Power Flows Using Genetic Algorithm.unkown
5, Issue 5, May 2016 A STATCOM Model for Optimal Power Flows Using ...The new model makes provisions for the explicit representation of the ...
An Advanced STATCOM Model for Optimal Power Flows using ....unkown
(0)191 334 2971 http://dro.dur.ac.uk An Advanced STATCOM Model for Optimal Power Flows using Newton's Method Behzad Kazemtabrizi, Member, IEEE, ...
An Advanced STATCOM Model for Optimal Power Flows Using ....unkown
An Advanced STATCOM Model for Optimal Power Flows Using Newton's Method Image not found PhImttrpaig:n/e/wtnwotwf.opuhnildadelphia.edu.jo/newlibrary/...
...STATCOM Models for Large-scale Newton-Raphson Power Flow ....unkown
(STATCOM) both models suitable for three-phase power flow studies using the Newton-Raphson in both frame-of-references: polar and rectangular co-ordinates...
PowerFlow Control of Grid Connected PV System using STATCOM.unkown
of Grid Connected PV System using STATCOM SP. ...(MLI), STATCOM, Powerflow model, Total Harmonics...STATCOM have been combined to make a new ...
...Study of SVC and STATCOM by using Continuation Power Flow ....unkown
A Comparitive Study of SVC and STATCOM by using Continuation Power Flow (CPF) Dr. V.CHAYAPATHY Associate Professor, Department of EEE R. V. College ...
Voltage stability and Power flow improvement using STATCOM ....unkown
August 2014 Voltage stability and Power flow improvement using STATCOM and ... New Delhi, India3 R.I.E.T., Faridabad, India4 Abstract: FACTS ...
...OF STATCOM ON IEEE-14 BUS SYSTEM USING POWER FLOW ANALYSIS.unkown
ISSN: 1992-8645 www.jatit.org E-ISSN: 1817-3195 PERFORMANCE ANALYSIS AND LOCATION IDENTIFICATION OF STATCOM ON IEEE-14 BUS SYSTEM USING POWER FLOW ...
...STATCOM with Six Pulse SPWM based VSC and its Power Flow ....unkown
7, July, 2012 Modeling of STATCOM with Six Pulse SPWM based VSC and its Power Flow Study T.Renuka1, P.Chandhrasekhar2 Adams Engineering College, ...
Load Flow Analysis on Statcom Incorporated Interconnected ....unkown
V (Jul Aug. 2014), PP 61-68 www.iosrjournals.org Load Flow Analysis on Statcom Incorporated Interconnected Power System Networks Using Newtonraphson ...
POWER FLOW CONTROL BY USING OPTIMAL LOCATION OF STATCOM.unkown
APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: 2230-8547; e-ISSN: 2230-8555 POWER FLOW CONTROL BY USING OPTIMAL LOCATION OF STATCOM S.B. ...
...Reactive Power Flow Based STATCOM Using Three Variant of PSO.unkown
Engineering 2012, 2(2): 1-7 DOI: 10.5923/j.ijee.20120202.01 Multi Objective Optimal Reactive Power Flow Based STATCOM Using Three Variant of PSO N....
Multi Objective Optimal Power Flow with STATCOM using DE in ....unkown
(Online) : 0974-5645 ISSN (Print) : 0974-6846 DOI : 10.17485/ijst/2015/v8i1/56654 Multi Objective Optimal Power Flow with STATCOM using DE in ...
Power Flow-Improvement in Transmission System by Using ....unkown
84-90 Power Flow-Improvement in Transmission System by Using Hysteresis Current Control 84 Pulse Statcom V.Iswarya1, K.S.S Prasad Raju2 ANDHRA UNIVERSITY...
...Using Multi-Connected DistributedPower Flow Controller (MC....unkown
Using Multi-Connected Distributed Power Flow ... This paper presents a new component within the ...7 Statcom Model The angle between the Vs and ...
...Reactive Power Flow Based STATCOM Using Three Variant of PSO.unkown
//www.researchgate.net/publication/283708029 Multi objective optimal reactive power flow based STATCOM using three variant of PSO DATASET FEBRUARY 2012 ...
Power Flow Simulation of a 6-Bus Wind Connected System and ....unkown
5, Issue 2, February 2016 Power Flow Simulation of a 6-Bus Wind Connected System and Voltage Stability Analysis by Using STATCOM Shaila Arif1 Lecturer,...
Determination of fault operation dynamical constraints for ....doc
STATCOM power flow modeling 5. Modeling and numerical simulation 5.1. ... a new high efficiency coreless transformer has been developed using polymer ...
更多相关标签: