PMBus? Power System Management Protocol Specification Part III – AVSBus

Revision 1.3 17 Mar 2014

www.powerSIG.org
? 2014 System Management Interface Forum, Inc. – All Rights Reserved

Filename: Last saved:

PMBus_Specification_Part_III_Rev_1-3X_20140317.docx 17 Mar 2014, 09:55

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

DISCLAIMER This specification is provided “as is” with no warranties whatsoever, whether express, implied or statutory, including but not limited to any warranty of merchantability, non-infringement, or fitness for any particular purpose, or any warranty otherwise arising out of any proposal, specification or sample. In no event will any specification co-owner be liable to any other party for any loss of profits, loss of use, incidental, consequential, indirect, or special damages arising out of this specification, whether or not such party had advance notice of the possibility of such damages. Further, no warranty or representation is made or implied relative to freedom from infringement of any third party patents when practicing the specification. Other product and corporate names may be trademarks of other companies and are used only for explanation and to the owner’s benefit, without intent to infringe. REVISION HISTORY
REV 1.3 DATE 17 Mar 2014 DESCRIPTION Revision 1.3, First public release of Part III EDITED BY Robert V. White Embedded Power Labs

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 2 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

Table of Contents 1 Introduction ............................................................................................................................................ 5
1.1 Specification Scope ...................................................................................................................... 5 1.1.1 Specification Structure ...................................................................................................... 5 1.1.2 What Is Included ................................................................................................................ 5 1.1.3 What Is Not Included In The PMBus Specification............................................................ 5 Specification Changes Since The Last Revision .......................................................................... 5 Where To Send Feedback And Comments .................................................................................. 5 Scope ............................................................................................................................................ 6 Applicable Documents .................................................................................................................. 6 Reference Documents .................................................................................................................. 6 Device, Signal and Parameter Names.......................................................................................... 6 3.1.1 AVSBus Signal Names ...................................................................................................... 6 3.1.2 Frame Elements ................................................................................................................ 6 Numerical Formats........................................................................................................................ 6 3.2.1 Decimal Numbers .............................................................................................................. 6 3.2.2 Floating Point Numbers ..................................................................................................... 6 3.2.3 Binary Numbers ................................................................................................................. 6 3.2.4 Hexadecimal Numbers ...................................................................................................... 7 3.2.5 Examples ........................................................................................................................... 7 Bit And Byte Order ........................................................................................................................ 7 Bit And Field Illustrations .............................................................................................................. 7 Abbreviations, Acronyms And Definitions ..................................................................................... 8 Compliance ................................................................................................................................. 10 Start Up And Operation .............................................................................................................. 11 Topology ..................................................................................................................................... 11 Operation .................................................................................................................................... 12 Modes ......................................................................................................................................... 13 5.3.1 3-Wire Mode .................................................................................................................... 13 5.3.2 2-Wire Mode .................................................................................................................... 13 Frame Size.................................................................................................................................. 13 Idle Bus Condition ....................................................................................................................... 13 Slave Resynchronization ............................................................................................................ 14 Bus Timeout ................................................................................................................................ 14 Clocking ...................................................................................................................................... 15 Electrical Interface ...................................................................................................................... 15 5.9.1 Timing .............................................................................................................................. 15 5.9.2 Electrical Drive Levels ..................................................................................................... 18 Data Launch................................................................................................................................ 18 Data Capture............................................................................................................................... 18 Data Format ................................................................................................................................ 19 Unknown Resource Selector ...................................................................................................... 19 Unavailable Resource ................................................................................................................. 19 <StartCode> .............................................................................................................................. 19 <SlaveAck> ................................................................................................................................ 19 <StatusResponse> .................................................................................................................... 20 CRC Verification ......................................................................................................................... 20 Data Validation............................................................................................................................ 21 Types Of Writes .......................................................................................................................... 21

1.2 1.3

2

Related Documents ................................................................................................................................ 6
2.1 2.2 2.3

3

Reference Information ........................................................................................................................... 6
3.1

3.2

3.3 3.4 3.5

4 5

General Requirements ......................................................................................................................... 10
4.1 4.2 5.1 5.2 5.3

Transport .............................................................................................................................................. 11

5.4 5.5 5.6 5.7 5.8 5.9

6

Protocol rules ....................................................................................................................................... 18
6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.10 6.11

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 3 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
6.11.1 Write and Commit ............................................................................................................ 21 6.11.2 Write and Hold ................................................................................................................. 21

7

Frame Definition ................................................................................................................................... 22
7.1 7.2 7.3 7.4 The Write Frame ......................................................................................................................... 22 The Read Frame ......................................................................................................................... 22 Frame Alignment......................................................................................................................... 24 Status Response Frame ............................................................................................................. 25 Voltage Read/Write (Command Data Type = 0000b) ................................................................. 26 Vout Transition Rate Read/Write (Command Data Type = 0001b) ............................................ 27 Current Read (Command Data Type = 0010b) .......................................................................... 27 Temperature Read (Command Data Type = 0011b) .................................................................. 27 Voltage Reset (Command Data Type 0100b) ............................................................................ 27 Power Mode Read/Write (Command Data Type = 0101b)......................................................... 28 Reserved for future use (Command Data Types 0110b to 1101b) ............................................ 28 AVSBus Status Read/Write (Command Data Type = 1110b) .................................................... 28 AVSBus Version Read (Command Data Type = 1111b)............................................................ 29 Manufacturer-Specific Read/Write (Group 1b, Data Types 0000b to 1111b)............................. 29

8

Data Types ............................................................................................................................................ 26
8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10

9 10 11 12

Communication From The AVSBus Slave To The AVSBus Master ........................................................ 29 PMBus? And AVSBus Device Mapping ................................................................................................ 29 Accuracy ............................................................................................................................................... 30 Summary Of Changes ........................................................................................................................... 31 Table of Figures

Figure 1. Bit Order Within A Field ................................................................................................................. 7 Figure 2. Example AVSBus Topology With One Master And One Slave ................................................... 12 Figure 3. Example AVSBus Topology With Multiple Links ......................................................................... 12 Figure 4. AVSBus 3-Wire Mode Connections ............................................................................................. 13 Figure 5. AVSBus 2-Wire Mode Connections ............................................................................................. 13 Figure 6. Timing Diagrams Reference Schematic ...................................................................................... 15 Figure 7. Timing diagram for AVS_MData .................................................................................................. 16 Figure 8. Timing diagram for AVS_SData................................................................................................... 16 Figure 9. <StatusResponse> Composition ................................................................................................ 20 Figure 10. Write Frame Structure ............................................................................................................... 22 Figure 11. Read Frame Structure ............................................................................................................... 23 Figure 12. Maximum Throughput ................................................................................................................ 25 Figure 13. Last Frame In A Sequence. ....................................................................................................... 25 Figure 14. Status Response Frame ............................................................................................................ 26 Figure 15. First Frame In A Sequence ........................................................................................................ 26 Figure 16. Example Power Management IC With Multiple PAGEs And Multiple AVSBus Ports ............... 30

Table of Tables
Table 1. Bit And Field Representation For Frame Illustrations ..................................................................... 7 Table 2. Abbreviations, Acronyms and Definitions Used In This Specification ............................................ 8 Table 3. Electrical Characteristics ............................................................................................................... 17 Table 4. Electrical Drive Levels ................................................................................................................... 18 Table 5. Frame Fields ................................................................................................................................. 23

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 4 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

1

Introduction
AVSBus is an interface designed to facilitate and expedite point-to-point communication between an ASIC , FPGA, or other logic, memory, or processor devices and a POL control device on a system for the purpose of adaptive voltage scaling. When integrated with PMBus, AVSBus is available for allowing independent control and monitoring of one or more rails within one slave. The communication protocol has been designed with provisions for future growth which include a mechanism for an ASIC to query the version of AVSBus supported. This will allow firmware to make the best use of new features as AVSBus evolves to satisfy system needs, and over time it will permit combining different generations of devices on a single system. For more information, please see the System Management Interface Forum Web site: http://www.powerSIG.org.

1.1
1.1.1

Specification Scope
Specification Structure The PMBus? specification is in three parts. Part I includes the general requirements, defines the transport, electrical interface and timing requirements of hardwired signals for PMBus. Part II defines the command language used with PMBus. Part III, this document, defines the transport, electrical interface, timing requirements and command language for AVSBus.

1.1.2

What Is Included This specification defines two protocols to manage power converters and a power system via communication over digital communication buses. PMBus can be used without the AVSBus extension, and AVSBus could be used on a simple system that does not implement the full PMBus spec, but the two are integrated seamlessly as AVSBus is a powerful extension to PMBus.

1.1.3

What Is Not Included In The PMBus Specification The PMBus specification is not a definition or specification of: ? A particular power conversion device or family of power conversion devices. ? A specification of any individual or family of integrated circuits. This specification does not address direct unit to unit communication such as analog current sharing, real-time analog or digital voltage tracking, and switching frequency clock signals.

1.2

Specification Changes Since The Last Revision
A summary of the changes between this revision and Revision 1.0 are shown in Section 12 at the end of this document.

1.3

Where To Send Feedback And Comments
Please send all comments by email to: TechQuestions@smiforum.org.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 5 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

2
2.1

Related Documents
Scope
If the requirements of this specification and any of the reference documents are in conflict, this specification shall have precedence unless otherwise stated. Referenced documents apply only to the extent that they are referenced. The latest version and all amendments of the referenced documents at the time the device is released to manufacturing apply.

2.2

Applicable Documents
Applicable documents include information that is, by extension, part of this specification. [A01] PMBus? Power System Management Protocol, Part I, General Requirements, Transport And Electrical Interface, Revision 1.3 [A02] PMBus? Power System Management Protocol, Part II, Command Language, Revision 1.3

2.3

Reference Documents
Reference documents have background or supplementary information to this specification. They do not include requirements or specifications that are considered part of this document. None in this revision.

3
3.1
3.1.1

Reference Information
Device, Signal and Parameter Names
AVSBus Signal Names The names of AVSBus signals corresponding to physical connections are given as “AVS”, followed by an underscore (“_”), followed by the signal name. An example is AVS_Clock.

3.1.2

Frame Elements Values for frame elements are represented by symbolic names shown in mixed-case monospaced font, and enclosed in angle brackets, like <CmdDataType> or <Select>.

3.2
3.2.1

Numerical Formats
All numbers are decimal unless explicitly designated otherwise. Decimal Numbers Numbers explicitly identified as decimal are identified with a suffix of “d”.

3.2.2

Floating Point Numbers Numbers explicitly identified as floating point are identified with a suffix of “f”.

3.2.3

Binary Numbers Numbers in binary format are indicated by a suffix of “b”.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 6 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
Unless otherwise indicated, all binary numbers are unsigned. All signed binary numbers are two’s complement. 3.2.4 Hexadecimal Numbers Numbers in hexadecimal format are indicated by a suffix of “h”. 3.2.5 Examples 255d ? FFh ? 11111111b 175d ? AFh ? 10101111b 1.2f

3.3

Bit And Byte Order
Considering that AVSBus interface frames have fields of multiple sizes, not limited to multiples of 8 bits, there is no concept of byte when determining the order in which information is transmitted. ? When a field of data is transmitted, the most significant bit (MSB) is sent first and the least significant bit (LSB) is sent last, regardless of the number of bits involved. This way the first bit transmitted corresponds to the sign bit in Two’s Complement notation. ? Fields are transmitted in the order in which they are depicted in the frame illustrations throughout the document: <StartCode> is sent first, followed by subsequent fields and ending with the last field on the right hand side of the diagram.

3.4

Bit And Field Illustrations
The transmission of bits within a field is illustrated in this section. In all cases, the least significant bit is indicated as Bit 0, as shown below.

Figure 1. Bit Order Within A Field This part of the specification describes transactions over AVSBus. The symbols used to describe the details of those transactions and protocols are shown in Table 1. Table 1. Bit And Field Representation For Frame Illustrations Symbol Meaning A rectangle with no shading indicates data sent from the host (bus master) to the slave device. A rectangle with a shaded interior indicates data sent from the slave device to the bus master.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 7 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
Symbol Meaning By default there is a rectangle for each field sent, not for each bit within a field. Typically the rectangle will have a number over it indicating the number of bits it represents. Shown here is the 3-bit CRC used for verifying the integrity of a transfer. It can be sent by the master or the slave, so it may be found shaded or clear. The <StartCode> sent from a bus master device to initiate a transfer is the 2-bit code 01b. When slaves send acknowledgement back to the bus master, they send a 2-bit code, represented by <SlaveAck>. Data fields are identified by a descriptive word, with the number of bits indicated above, as shown here for a 16-bit voltage value.

3.5

Abbreviations, Acronyms And Definitions
Table 2. Abbreviations, Acronyms and Definitions Used In This Specification Term ACK, <SlaveAck> <AVSBus_Status> Definition Acknowledge. The response from a slave indicating that it has received a transfer. The encoding used for the 2 bits is explained in Section 6.7. A 16-bit field composed by concatenating multiple status bits. The associated <CmdDataType> as explained in Section 8.8 describes those flags and how they can be read by the AVSBus Master. It should not be confused with <StatusResponse>. A signal is asserted when the signal is true. See Negate. Adaptive Voltage Scaling. AVS is used by a device to control its supply voltage, generally to minimize power consumption for a given operating condition. When referring to a bit or bits, this means setting the value to zero. A generic term to refer to the actual data carried in a frame, which in the most typical case is a voltage setting. Command codes, selector fields, acknowledgement codes and CRC are not command data. They provide the context for the command data to be properly interpreted. Page 8 Of 31

Assert, Asserted AVS

Clear Command Data, <CmdData>

? 2014 System Management Interface Forum, Inc. All Rights Reserved

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

Term

Definition

Command Data Type, An identifier used to differentiate between the types of data <CmdDataTy contained in the <CmdData> field of a given AVSBus frame, such as voltage or temperature. pe> CRC A 3-bit Cyclic Redundancy Code used to detect errors in a transfer, which allows the receiving device to discard presumably corrupted data. A non-volatile memory store most typically used by the device manufacturer to store default values. To instruct the device to stop the power conversion process and to stop delivering energy to the output. The device’s control circuitry remains active and the device can communicate via control buses. To instruct the device to start the power conversion process and to start delivering energy to the output. A host must be an AVSBus Master. There is only one host per AVSBus instantiation. To stop the transfer of energy to the output while a given condition, such as excessive internal temperature, is present. Least significant bit A master is a device that issues commands, generates the clock, and terminates the transfer. Master Data sent via the output port AVS_MData of an AVSBus Master for sending bits to its AVSBus Slave, which is connected to the input port AVS_SData of the slave device. See also SData. Most significant bit A signal is negated when the signal is false. See Assert. Point-of-load. Generally refers to a power supply output The identifier for a rail in the device, used as <Selector> in AVS Commands. Slave Data sent via the output port AVS_SData of an AVSBus Slave for sending bits to its AVSBus Master, which is connected to the input port AVS_MData of the master device. See also MData. Page 9 Of 31

Default Store Disable, Disable Output

Enable, Enable Output Host Inhibit LSB Master MData

MSB Negate, Negated POL Rail Rail Selector, <RailSel> SData

? 2014 System Management Interface Forum, Inc. All Rights Reserved

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

Term

Definition

<Selector> The identifier that indicates what instance of a device’s resources is the target of a command. <Selector> typically refers to a rail number, in which case it is depicted as <RailSel>. Set Shut Down When referring to a bit or bits, this means setting the value to one. Disable or turn off the output. This generally implies that the output remains off until the device is instructed to turn it back on. The device’s control circuit remains active and the device can respond to commands received via control buses. A slave is a device that is receiving or responding to a command. <StartCode A 2-bit field used to mark the beginning of a Master sub-frame. > <StatusResponse> A 5-bit field composed by concatenating multiple flags. There is no associated <CmdDataType>. The Status Response field will be sent by the AVSBus Slave twice in every frame, as explained in Section 9. It should not be confused with <AVSBus_Status>. When used to define a binary value, X means that the value of that bit is a “don’t care” that can be safely ignored. When used in examples, X means that the example applies to any value of that bit. It is a “don’t care” for the purpose of the example.

Slave

X

4
4.1

General Requirements
Compliance
The AVSBus protocol is intended to cover a wide range of power system architectures and converters, as it can be used stand-alone or as a complement to PMBus. AVSBus Slaves may not support all of the available features, functions and commands. To be compliant to the AVSBus specification: ? If a device accepts an AVSBus command code, it must execute the associated function as described in Part III of the PMBus specification (this document). ? If a device does not accept a given AVSBus command code, it must respond as described in Section 6. ? A device must support voltage scaling through implementation of writing voltages as specified in Section 8.1. ? A device configured for 3-wire operation must support reading of <AVSBus_Status> and sending of <StatusResponse>. Page 10 Of 31

? 2014 System Management Interface Forum, Inc. All Rights Reserved

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
? A device must implement the Resynchonization mechanism described in Section 5.6.

A device may or may not support additional operations, such as reading or writing Vout Transition Rate, reading Temperature, or reading Current. This does not affect compliance.

4.2

Start Up And Operation
AVSBus devices, upon application of power, must start up and begin operation in a controlled manner, as programmed internally or externally, without requiring communication from either PMBus or AVSBus. Furthermore, enabling and disabling the power conversion process must also occur independently of AVSBus communication. Control over enabling and disabling power conversion, as well as all operational parameters, is best achieved through PMBus, with AVSBus relegated to its intended purpose of controlling voltage scaling. PMBus determines if the AVSBus Master gets control over the settings of the AVSBus Slave, and can take that control away. However, regardless of whether control is given to the AVSBus Master or not, PMBus can always read data, and the AVSBus Master can always read data. In fact, the AVSBus Master may attempt to write data at any time, but any writes that occur while AVS has not been given control via PMBus will result in the AVSBus Slave responding with the <SlaveAck> for “Unavailable Resource”. See Section 6.5 for more information.

5
5.1

Transport
Topology
AVSBus is a 3-wire communication link designed to provide bidirectional communication between one powered device (such as an ASIC, FPGA or processor) and one slave for controlling voltage scaling. The three wires used for communication are AVS_Clock, AVS_MData, and AVS_SData. ? AVS_MData is driven by the AVSBus Master and carries data to the slave, ? AVS_SData is driven by an AVSBus Slave and carries data to the master, and ? AVS_Clock is driven by the master and clocks data for both the AVS_MData and AVS_SData lines. An optional 2-wire unidirectional implementation is allowed using only AVS_Clock and AVS_MData. In this limited implementation, the AVSBus Master will never receive acknowledgments, status or data back from a slave device. Note: AVSBus is behaviorally and electrically similar to SPI bus without chip select lines: ? AVS_MData and AVS_SData are equivalent to MOSI and MISO. ? AVS_Clock is equivalent to CLK of the SPI bus. The only topology supported is one-to-one dedicated link between an AVSBus Slave and its controlling AVSBus Master. In the example shown in Figure 2 the ASIC (or FPGA or processor) is the AVSBus Master and the other device in the link is the AVSBus Slave. The AVSBus Slave may support one or more voltage rails, each one individually addressable by the AVSBus Master. In either case each rail may be composed of multiple phases.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 11 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

AVSBus Master

AVSBus

AVSBus Slave

ASIC/FPGA/Processor
Figure 2. Example AVSBus Topology With One Master And One Slave In the example shown in Figure 3 one ASIC (or FPGA or processor) includes two AVSBus Masters, each of which communicates by a dedicated link to one AVSBus slave.

AVSBus Master

AVSBus

AVSBus Slave

AVSBus Master

AVSBus

AVSBus Slave

ASIC/FPGA/Processor
Figure 3. Example AVSBus Topology With Multiple Links

5.2

Operation
Each type of device in a link performs specific complementary functions: 1. The AVSBus Master must initiate all data transfers. Besides setting voltages, a master may also use AVSBus to request data of various types from the slave. The master must guarantee that AVS_MData is held at a logic value ‘1’ when the clock is not running: during initialization prior to any bus transfers, as well as during idling between frames. AVS_MData is not allowed to be at a logic value ‘0’ when the clock starts. 2. The AVSBus Slave listens for and may respond to master commands but cannot initiate a transfer under any circumstances. In general the slave must guarantee that AVS_SData is held at a logic value ‘1’ when the clock is not running: during initialization prior to any bus transfers, between frames, as well as at any time during a transfer when the slave is not sending data to the master. An exception to this rule is that the AVSBus Slave will set AVS_SData to a logic value ‘0’ when it needs to alert the AVSBus Master to start a frame so that it can send <StatusResponse>. See the Section 9 for more details.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 12 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3 5.3
5.3.1

Modes
There are two different modes of operation for AVSBus, 3-wire mode and 2-wire mode. 3-Wire Mode The 3-wire mode is the complete implementation of AVSBus that allows a master to receive acknowledgements from slaves in response to write operations, to read back data and configuration from them, and to receive <StatusResponse> in every frame. The figure below illustrates a typical implementation. This mode requires AVS_SData.

AVS_Clock AVSBus Master AVS_MData AVS_SData AVSBus Slave

Figure 4. AVSBus 3-Wire Mode Connections 5.3.2 2-Wire Mode The 2-wire mode is a partial implementation of AVSBus in which a slave does not come with the optional AVS_SData output, thus rendering it incapable of sending any data back to its master.

AVS_Clock AVSBus Master AVS_MData AVSBus Slave

Figure 5. AVSBus 2-Wire Mode Connections

5.4

Frame Size
AVSBus frames are 64 bits long. There are two different types of frames, as explained in Section 7.

5.5

Idle Bus Condition
The bus is considered idle in two cases: 1. When the clock is suspended between frames.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 13 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
In this case the state of AVS_MData is a “Don’t care” to the slave, but it is required that the line be kept high to enable proper detection of <StartCode> when the clock resumes. The state of AVS_SData is relevant to the master even when the clock is suspended. Considering that the slave has no control over when the master may start providing a clock, a slave that wants to alert the master to the fact that there has been an important status change will simply change AVS_SData from its default state (Logic 1) to a signaling state (Logic 0), and keep the signaling state until the master initiates a frame. Except for this interrupt scenario, the slave must keep the line high when the clock is suspended. As a consequence both lines must be held high while the clock is suspended, to support detection of start codes and for requesting a frame. 2. When, even in the presence of a clock, no frames are being transmitted. Whenever the clock is running AVS_MData must be held high (Logic 1) if the AVSBus Master is not sending any data. Again that level is a precondition for issuing the <StartCode> which consists of the two bit sequence 01b. In effect, the first logic 0 encountered while the bus has been in idle condition marks the beginning of a transfer, as there is no concept of persistent 8-bit boundaries when the clock runs in idle condition. Likewise, AVS_SData should be held high (Logic 1) when no frames are being transmitted by the AVSBus Slave. Just like when the clock is suspended, a slave that wants to alert the master to the fact that there has been an important status change will simply change AVS_SData from its default state (Logic 1) to a signaling state (Logic 0), and keep the signaling state until the master initiates a frame.

5.6

Slave Resynchronization
An AVS Slave must implement the resynchronization mechanism to recover in case noise in the line or some other artifact has caused it to reach an incorrect state. Receiving 34 clock pulses while AVS_MData is held high will cause a slave to resynchronize its communication interface, and wait for the next <Start_Code>. For the resynchronization mechanism to work correctly, the AVSBus Slave must keep counting ones as long as it is receiving clock pulses, and reset the count whenever it receives a zero. This will ensure the earliest possible detection of a sequence of 34 ones. It is recommended for the master to resynchronize the slave at startup, and to do so periodically afterwards.

5.7

Bus Timeout
AVSBus does not require that slaves implement bus timeout functions. Such a feature would be useful for detecting when AVS_Clock has stalled so that the slave can take some protective action, but it would impose additional burdens on the slave which may be too costly. Though not required, a mechanism for detecting AVSBus timeout should be given serious consideration and implemented whenever possible.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 14 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3 5.8 Clocking
The bus can transfer data continuously when needed, which would require an uninterrupted clock from the master. For periods with no bus activity, the master can suspend AVS_Clock and then restart it later when needed. A suspended or inactive clock will be held in a logic ‘0’ state, to ensure that whenever the clock starts, the first detectable edge is the rising edge. The following section describes the timing requirements of AVS_Clock.

5.9

Electrical Interface
The AVSBus Master always provides AVS_Clock and AVS_MData (Master Data), and it may or may not have an input for AVS_SData (Slave Data), depending on whether 2wire or 3-wire Mode is implemented. The logic level for data and clock lines must be constant for any given application. An AVSBus-compliant device will have a predetermined I/O logic level within the specified range. Since the AVS_Clock and AVS_MData lines are always driven by the master and AVS_SData is always driven by the slave, there is no need for pull-up resistors for normal operation. However, it is recommended that the system be designed with weak pull-up resistors for robustness, so that all three lines are at known voltage levels in case one of the devices is not powered up or not present.

5.9.1

Timing The following diagrams and tables illustrate the timing requirements for AVSBus. Notice that the Slave-to-Master data path is grayed-out in the schematic, since this is optional functionality. For the same reason, the timing tables have separate figures for launch and capture by the Master and the Slave. In this interface, both master and slave launch data from the rising edge of the clock, and they both capture data using the falling edge.

Figure 6. Timing Diagrams Reference Schematic ? 2014 System Management Interface Forum, Inc. All Rights Reserved Page 15 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

Figure 7. Timing diagram for AVS_MData

tp thigh AVS_Clock @ Master tdelay AVS_Clock @ Slave tlaunch-slave AVS_SData @ Slave trise AVS_SData @ Master tdelay thold-master tsetup-master tdelay VIH VIL tfall VOH VOL tcapture-master VIH VIL tlow VOH VOL

Figure 8. Timing diagram for AVS_SData ? 2014 System Management Interface Forum, Inc. All Rights Reserved Page 16 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
The timing diagrams, Figure 7 and Figure 8, show a skew in the clock and data lines, labeled tdelay, which corresponds to transmission delays on the board. A comparable delay affects the data lines. All times are measured at the pads of the master or the slave, as pertinent.

Table 3. Electrical Characteristics Parameter tp fclock thigh tlow trise tfall tdelay Description Period for active clock Frequency for active clock Duration of the high-phase of clock Duration of the low-phase of clock Rise time for data. Fall time for data. Time for signals to propagate from one device to the other one. 10 tp/2 1.5% of tp 1.5% of tp 4 3 3 Min. 20 1/tp ns ns ns ns ns Typ. Max. 200 Units ns

Master-to-Slave data path tlaunch-Master Time from rising clock edge in Master to data-out transition at Master's data-out port. Time from falling clock edge in Master to data capture inside Slave. Time from data-out edge in Master to capture clock edge in Slave. Time from capture clock edge in Slave to data-out edge in Master (for next bit). 0 2 ns

tcapture-Slave tsetup-Slave thold-Slave

tdelay 2 + tdelay 2

2 + tdelay

ns ns

tlow

ns

Slave-to-Master data path tlaunch-Slave tcapture-Master tsetup-Master thold-Master Time from rising clock edge in Master to data-out transition at Slave's data-out port. Time from falling clock edge in Master to data capture inside Master. Time from data-out edge in Slave to capture clock edge in Master. Time from capture clock edge in Master to data-out edge in Slave (for next bit). 2 + tdelay 0 2 + tdelay 2 tlow 4 + tdelay 2 Note 1 ns ns ns ns

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 17 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
Note 1: The clock used by the slave is a delayed version of the clock in the master. For that reason, launching data from the slave starts later than launching from the master, and relatively speaking, capturing by the master comes earlier. If tdelay is large on a given board, it may be necessary to increase thigh to compensate and give more time for the data to go from the slave to the master. 5.9.2 Electrical Drive Levels The electrical drive levels for AVSBus are independent of those for PMBus. Special care should be taken to ensure that the power sequencing is robust enough that all interoperability is not compromised. The general requirement is that the master will determine the drive levels and the slave must work with those levels. The simplest way to do this is to have a common VDD for the master and the slave I/O circuitry. There are also adaptive detect and drive level adjustment mechanisms that could be used by the slave to match the drive levels supplied by the master. Table 4. Electrical Drive Levels Limits Parameter VDD VIL VIH VOL VOH ILEAK-PIN Description Min AVS Master bus voltage AVSBus signal Input Low voltage AVSBus signal Input High voltage AVSBus signal Output Low voltage AVSBus signal Output High voltage Input Leakage per pin 80% VDD -10 +10 60% VDD 20% VDD 0.9 Max 3.63 40% VDD V V V V V ?A 1 V to 3.3 V ±10% Units Comments

6

Protocol rules
For the rules outlined below there is no distinction between master and slave unless indicated. Instead, the role of transmitter or receiver that they play at any given time is what matters.

6.1

Data Launch
A transmitter launches data on the rising edge of the clock.

6.2

Data Capture
A receiver captures data on the falling edge of the clock.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 18 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3 6.3 Data Format
Some AVSBus data types represent numeric data, others represent bit fields with custom encoding. Those representing numeric data use standard Two’s Complement representation, with data getting sign-extended to fit the data type size. Those that consist of bit fields are padded with zeroes. In either case the resulting data can be described as LSB-aligned. When a PMBus system is configured to use any data format other than Two’s Complement (for example, the DIRECT data format), it is up to the manufacturer of the AVSBus Slave to determine how to make the data conversion to and from Two’s Complement, and to specify in the documentation any limitations.

6.4

Unknown Resource Selector
An AVSBus Slave that receives a command for an unknown resource will respond with a special <SlaveAck> code that indicates that no action was taken because the resource does not exist. See Section 6.7 An unknown resource may be an unsupported <CmdDataType> (e.g., attempting to read temperature on a device that does not provide temperature values, or to write a readonly data type like temperature or current) or a selector for a non-existing instance (e.g., referring to rail 3 when there are only 2 rails).

6.5

Unavailable Resource
An AVSBus Slave that receives a read or a write frame for one of its resources which is not available will respond with a special <SlaveAck> code that indicates that no action was taken because the operation cannot be carried out at the present time. See Section 6.7 A resource that is not available may be in a disabled state (e.g., attempting to set a target voltage on a rail that is turned off) or be busy (e.g., attempting to read temperature when the A/D converter is occupied in some other measurement and there is no temperature available to send back).

6.6

<StartCode>
AVS_MData having a default state of ‘1’ sets the conditions for the detection by a slave of the start of a new frame through a <StartCode> since the first bit of that code is a ‘0’ as indicated in Table 5.

6.7

<SlaveAck>
Whenever an AVSBus Master sends a command, the AVSBus Slave will send back a 2bit acknowledgment. The two bits encode the following four states: ? ? ? ? 00b: Good CRC, action taken. 01b: Good CRC, but no action is taken due to resource busy. 10b: Bad CRC, no action is taken. 11b: Good CRC, but invalid selector, invalid data type (e.g. non-existent command) or incorrect data (e.g. out of range data value). No action is taken.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 19 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3 6.8 <StatusResponse>
Every time an AVSBus Master initiates a frame, the slave must send back a response that can be used by the master to assess the general condition of the slave. This is a 5bit field formed like this:

1 <Vdone>

1 <StatusAlert>

1 <AVS_Control>

1

1

<MfrSpcfc_Stts1> <MfrSpcfc_Stts2>

Figure 9. <StatusResponse> Composition Where: ? ? <VDone> corresponds to the combined <VDone> bits of all active rails, as described in Section 8.8. <StatusAlert> indicates that at least one of the status bits in Section 8.8 is asserted, excluding <VDone>. The AVSBus Master should consider issuing a read for AVS Status. Notice that since <VDone> is sent by itself in the response, it is excluded from the conditions that cause <StatusAlert> to be set, so as to avoid triggering unnecessary read operations. <AVS_Control> indicates whether AVSBus is controlling at least one of the device’s output or not. When AVSBus is controlling at least one of the outputs, it returns 1b. When AVSBus is not in control of any output, it returns 0b. <MfrSpcfc_Stts1> a status bit whose definition is left up to the AVSBus Slave’s manufacturer. It must be defined with positive logic: the status is considered active (set) when the value returned is 1b; otherwise it will be returned as 0b. <MfrSpcfc_Stts2> another status bit whose definition is left up to the AVSBus Slave’s manufacturer. It must follow the same rules.

?

?

?

?

6.9

CRC Verification
Support for 3-bit CRC is required for all AVSBus devices. The transmitter uses the CRC-3 polynomial on the first 29 bits in a sub-frame, and it generates the CRC code to send. The receiver then takes the entire sub-frame, including the CRC itself, and uses the same polynomial to confirm integrity of the data by verifying the CRC. The entire sub-frame is covered by the CRC. The polynomial used to calculate the 3-bit CRC is: CRC(x) = x^0 + x^1 + x^3 If data being transferred does not pass CRC verification, the action taken by the receiver depends on what device is playing that role. An AVSBus Master that receives questionable data from a slave will discard the data. It should initiate the transfer once more. An AVSBus Slave that receives questionable command/data from a master will send the corresponding <SlaveAck> code indicating that the specific action requested was not performed, and ignore the command/data.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 20 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3 6.10 Data Validation
It is crucial that an AVSBus Slave be able to protect itself and its loads by determining if a voltage setting is unacceptable. To that effect it is required that a compliant AVSBus Slave perform a range check for each voltage write. If the value is larger than the maximum or smaller than the minimum provided, the slave will respond with the <SlaveAck> code for “Incorrect Data”, described in Section 6.7 The PMBus commands VOUT_MAX and VOUT_MIN shall be used for providing the range used by AVSBus for voltage validation.

6.11

Types Of Writes
AVSBus offers two types of writes, one of which offers functionality that allows the AVSBus Master to synchronize changes across rails in a device. It is important to notice that the PMBus setting of WRITE_PROTECT does not have any effect on AVSBus writes. The PMBus WRITE_PROTECT command is not meant to prevent a device from managing its own power.

6.11.1

Write and Commit The traditional write operation: This type of write will also commit values held for other instances of the same command data type as described for “Write and Hold” below. Every <CmdDataType> that supports writing must support Write and Commit which is encoded as 00b in <Cmd>.

6.11.2

Write and Hold A very flexible write operation in which the value carried in the command data field is stored in a holding area but does not take effect (is not committed). What happens to the stored value depends on future commands, as follows: ? If a value is written with Write and Hold for a given instance of a command data type, a subsequent Write and Commit command for any instance of the same command data type will cause the value being held to be committed. ? If a value is written with Write and Hold for a given instance and then again later with another Write and Hold command for the same instance, the first value is discarded and never used. The new value is held to be committed later. ? If a value is written with Write and Hold and then a new value is written for the same instance with a Write and Commit command, the first value is discarded and never used. For example, an AVS Master could use Write and Hold for programming new transition rates and voltages in 2 rails of a device, and have them there ready for later use. At a later time it would issue a Write and Commit command for the transition rate of the third rail, which would also commit the transition rates of the other two, while the voltages remain uncommitted. For a simple AVSBus Slave with only one instance of a command data type, use of the Write and Hold command is pointless: the only way to commit a value written with it is to use a command that replaces it. Supporting Write and Hold, which is encoded as 01b in <Cmd> is not mandatory, unless clearly stated in this specification for individual command data types.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 21 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

7

Frame Definition
The communications protocol consists of two frame layouts: a Write frame and a Read frame. The frames themselves have two segments (sub-frames): the Master segment (sent over AVS_MData), which always begins with <StartCode>, and the Slave segment (sent over AVS_SData). There is a causal relationship between sub-frames: ? A Master Write sub-frame is immediately followed by a Slave Write sub-frame. ? A Master Read sub-frame is immediately followed by a Slave Read sub-frame. According to that description, the two sub-frames of a frame happen sequentially one after the other. This is the default behavior, and it is depicted in the illustrations that accompany the frame descriptions below, which are followed by detailed field definitions in Table 5.

7.1

The Write Frame
This type of frame contains the following fields in the Master sub-frame, carried in the AVS_MData line: ? ? ? ? ? ? ? ? ? ? ? ? <StartCode> <Cmd> (Either 00b or 01b in write frames) <CmdGroup> <CmdDataType> <Select> <CmdData> <CRC> <SlaveAck> 0b <StatusResponse> <Reserved_21> (Always all 1’s) <CRC>
1 X 4 4 16 3 <CmdDataType> <Select> <CmdData> <CRC> 2 <SlaveACK> 1 0 5 <StatusResp> 21 3

As well as the Slave sub-frame, carried in the AVS_SData line:

2 2 01 0X

<Reserved> <CRC>

Figure 10. Write Frame Structure

7.2

The Read Frame
This type of frame contains the following fields in the Master sub-frame, carried in the AVS_MData line: ? ? ? <StartCode> <Cmd> (Always 11b in read frames) <CmdGroup> Page 22 Of 31

? 2014 System Management Interface Forum, Inc. All Rights Reserved

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
? ? ? ? ? ? ? ? ? ? <CmdDataType> <Select> <Reserved_16> (Always all 1’s) <CRC> <SlaveAck> 0b <StatusResponse> <CmdData> <Reserved_5> (Always all 1’s) <CRC>

As well as the Slave sub-frame, carried in the AVS_SData line:

Figure 11. Read Frame Structure Table 5. Frame Fields Field Name <StartCode> <Cmd> Size (bits) 2 2 Description 01b is the code that activates the frame-decoding logic. Command code that determines the action that the master requires: ? 11b: Read data. ? 10b: Reserved. ? 01b: Write data and hold, but do not commit (leave pending). ? 00b: Write data and commit all pending voltage writes. Qualifier to distinguish between two groups of data types: ? 0b for fully defined AVSBus data types. ? 1b for manufacturer-specific data types.

<CmdGroup>

1

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 23 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

Field Name <CmdDataType>

Size (bits) 4

Description Type of data to which <Cmd> applies. For <CmdGroup> = 0b, the data types are: ? 0000b: Target rail voltage. ? 0001b: Target rail Vout transition rate. ? 0010b: Rail current (read only). ? 0011b: Rail temperature (read only). ? 0100b: Reset rail voltage to default value (write only). ? 0101b: Rail power mode. ? 0110b to 1101b: Reserved command data types. ? 1110b: AVSBus Status ? 1111b: AVSBus Version For <CmdGroup> = 1b the definition of the data types is found in the device’s product literature. Selector field to differentiate between instances of a command data type on a device. ? For <CmdGroup> = 0b, this is a rail selector: <RailSel>. ? For <CmdGroup> = 1b, this is left up to the device manufacturer to specify. The value 1111b is called a “Broadcast Frame”. It applies to all instances. For example, it applies to all rails when the selector corresponds to <RailSel>. Broadcast only makes sense for writes, not reads, with the exception of AVSBus Status Read. See Section 8.8. Data being transferred. A 3-bit field used to detect the presence of errors in the transmission of a sub-frame. A number of bits reserved for future use. Reserved bits must be sent as all 1’s. Response from a slave. AVSBus status bit that indicates whether the target voltage has been reached. For more details, see Section 8.8. AVSBus status bit that indicates to the master that there may be important information for it in the slave. For more details, see Section 8.8.

<Select>

4

<CmdData> <CRC> <Reserved_N> <SlaveAck> <VDone> <Alert>

16 3 N 2 1 1

7.3

Frame Alignment
Frames can happen in complete isolation from each other, sequentially one after the other, or overlapping. How frames occur with respect to each other over time affects the overall throughput of the bus and determines how the gaps are filled.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 24 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
In the most efficient use of bandwidth, an AVSBus Master will continually send frames back to back. This is what such a sequence would look like:

Figure 12. Maximum Throughput Notice that the two pieces of Frame_Y in the middle of the diagram happen back to back, as illustrated earlier for read and for write frames. However, unlike those illustrations, the AVSBus Master initiated <Master_sub-frame_Y> while the AVSBus Slave was sending <Slave_sub-frame_X>. Note that when master and slave sub-frames overlap as described, <StartCode> for the upcoming frame occurs exactly at the same time as <SlaveAck> for the frame currently in progress. This overlapping can continue for as long as there are more frames for the master to initiate, but sooner or later the AVSBus Master will have nothing to send. When that occurs, there is no <StartCode> overlapping the last <SlaveAck>. Instead, AVS_MData must be returned to its default state (high) until the end of the slave subframe. Then since the channel goes idle, both AVS_MData and AVS_SData stay high indefinitely. This is what the end of a sequence would look like:

Figure 13. Last Frame In A Sequence.

7.4

Status Response Frame
At some point there will be more frames to send, and the first <StartCode> is issued by the AVSBus Master. With the frame definitions we have so far, there would be no alternative for the AVSBus Slave but to keep AVS_SData high. However, there is a special type of slave sub-frame created to take advantage of that bandwidth: the Status Response Frame. There is no <SlaveAck> to send, since those are always part of the reply to a master sub-frame, and in this situation the AVSBus Master is not awaiting a reply. There is no <CmdData> either, since there is no read command pending completion. But <StatusResp> can bring valuable and timely information to the master, and that is the purpose of the Status Response Frame. The Status Response Frame is structured as shown in Figure 14 in the context of a generic master sub-frame. The zero at the 3rd bit of the frame is followed by the five bits that make up <StatusResponse> which in turn are followed by all 1’s padding to preserve the frame size, and finally a standard <CRC>.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 25 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3 2 01 2 <Prefix> 30 <Master_sub-frame fields combined> 1 0 5 <Status_Resp> 21 All 1's (Idle) 3 <CRC>

Figure 14. Status Response Frame The <Prefix> is a 2-bit placeholder at the beginning of the frame. Only two values are valid for this prefix. ? If the slave signals an interrupt by lowering AVS_SData prior to the appearance of <StartCode>, it would naturally be expected to be 00b, providing continuity. ? If the slave did not signal an interrupt, AVS_SData is at its default high state when <StartCode> appears, and it would retain that value so it can be expected to be 11b.

Considering that it is conceivable that the AVSBus Slave may not be ready for the <StartCode>, it is necessary that the AVSBus Master be designed to watch out for the AVS_SData set low during the 3rd bit of the first byte of a Status Response frame. As long as the line is low during that bit, it should accept <StatusResponse> as valid. <StatusResp> is formed by concatenating <VDone>, <Alert> and other flags as outlined in Section 8.8. The format of the Status Response Frame shown here is directly compatible with the reply of a slave to a command from the master, with two differences: ? ? <Prefix> is replaced with <SlaveAck> when the slave is responding to a master command. The all 1’s idle field corresponds to the rest of the slave’s response, which is different for a read than for a write.

Incorporating the concept of the Status Response Frame, the first frame in a sequence of overlapping frames would appear as shown in Figure 15.

Figure 15. First Frame In A Sequence

8
8.1

Data Types
This section describes in detail each one of the commands supported by AVSBus.

Voltage Read/Write (Command Data Type = 0000b)
This type allows the AVSBus Master to read or write a new voltage target for a rail on an AVSBus Slave. See Part II, Section 12.1 for a full description of the handoff between AVSBus and PMBus control of the output voltage. In this case <Select> is <RailSel>, and <CmdData> is <Voltage> which is a 16-bit unsigned integer field with 1 LSB = 1 mV.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 26 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
If the new voltage is too high or too low, as determined by the values set through the PMBus commands VOUT_MIN and VOUT_MAX, the AVS Slave will respond with the <SlaveAck> for incorrect data.

8.2

Vout Transition Rate Read/Write (Command Data Type = 0001b)
This type allows the AVSBus Master to read or write a new transition rate for a rail on an AVSBus Slave. In this case <Select> is <RailSel>, and <CmdData> is <TransRates> which is a 16-bit field composed of two fields: <RiseTransRate> and <FallTransRate>. Each field is an 8-bit unsigned integer with 1 LSB = 1 mV/?s. The fields are concatenated in the order they were described: <RiseTransRate> is sent first, followed by <FallTransRate>. The AVSBus Slave will use <RiseTransRate> when the rail voltage is increasing, and <FallTransRate> when the rail voltage is decreasing. When AVSBus is enabled, the initial transition rates will be specified by the AVSBus Slave manufacturer and given in the product literature.

8.3

Current Read (Command Data Type = 0010b)
This type allows the AVSBus Master to read the current for a rail on an AVSBus Slave. Writes are not supported. In this case <Select> is <RailSel>, and <CmdData> is <Current> which is a 16-bit unsigned integer field with 1 LSB = 10 mA. AVSBus does not dictate whether the value being read is filtered in any particular way, leaving it up to each specific AVSBus Slave’s manufacturer product literature to clearly describe if filtering is used, and whether it is configurable by PMBus.

8.4

Temperature Read (Command Data Type = 0011b)
This type allows the AVSBus Master to read the temperature for a rail on an AVSBus Slave. Writes are not supported. In this case <Select> is <RailSel>, and <CmdData> is <Temperature> which is a 16bit signed integer field with 1 LSB = 0.1 °C. AVSBus does not dictate whether the value being read is filtered in any particular way, leaving it up to each specific AVSBus Slave’s manufacturer product literature to clearly describe if filtering is used, and whether it is configurable by PMBus.

8.5

Voltage Reset (Command Data Type 0100b)
This type allows the AVSBus Master to force a “Predefined Value” for an AVSBus Slave rail, particularly while handling exceptions that could otherwise cause damage. Since there is no associated data for this command, <CmdData> must be set to all 0’s. The predefined value is determined by the manufacturer of the AVSBus Slave. It is envisioned that this command would be particularly useful when used in broadcast mode to all the rails in a device (by setting <RailSel> to all 1’s), giving the AVSBus Master the ability to reset all rails to their own individual reset values in a single frame. In this case <Select> is <RailSel>, and <CmdData> is 00h.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 27 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3 8.6 Power Mode Read/Write (Command Data Type = 0101b)
This type allows the AVSBus Master to set the mode of operation for the output of an AVSBus Slave rail. There are 8 possible settings: four predefined settings referred to as the “AVSBus Standard Power Modes”, and four manufacturer-specific modes. In this case, <Select> is <RailSel> and <CmdData> is <PowerMode> which is a 3-bit field with the following encoding: ? 000b – Maximum Efficiency ? 001b – Reserved ? 010b – Reserved ? 011b – Maximum Power ? 100b to 111b: Manufacturer-specific settings Following the bit justification rule, the 3-bit <PowerMode> field is aligned on the LSB of the <CmdData> field, with all preceding bits filled with zeroes. Power mode is also accessible through the PMBus interface. See Part II, Section 14.13 for more details.

8.7 8.8

Reserved for future use (Command Data Types 0110b to 1101b) AVSBus Status Read/Write (Command Data Type = 1110b)
This type allows the AVSBus Master to read the <AVSBus_Status> of an AVSBus Slave, or to clear the slave’s <AVSBus_Status> by a write. A clear operation for AVSBus shall not affect the corresponding status bits for PMBus status registers. This implies that the bits in <AVSBus_Status> that reflect PMBus status bit must either be copies of those in bits in their own register or that some form of a mask must be used to present a cleared value to the AVSBus. The status consists of 16 bits concatenated in the following order: ? <VDone> - A single bit flag that will be 0b while the rail is off or powering up, it will change to 1b as soon as the voltage has reached the set operating point, and will again transition to 0b when a new target is committed. The threshold for determining when the output has reached the target is defined by the manufacturer of the AVSBus Slave, and must be clearly described in the product documentation. <OCW> - The IOUT_OC_WARNING (Output over-current) flag that is found as bit [5] of PMBus command STATUS_IOUT. <UVW> - The VOUT_UV_WARNING (Output under-voltage) flag that is found as bit [5] of PMBus command STATUS_VOUT. <OTW> - The IOUT_OT_WARNING (Over-temperature) flag that is found as bit [6] of PMBus command STATUS_TEMPERATURE. <OPW> - The POUT_OP_WARNING (Output over-power) flag that is found as bit [0] of PMBus command STATUS_IOUT. <Reserved_3> - Three bits reserved for future use. Until defined this field should be returned as 000b.

? ? ? ? ?

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 28 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
? <MfrSpcfc_8> - Eight bits whose definition is left up to the AVSBus Slave. They must be defined with positive logic: the status is considered active (set) when the value returned is 1b; otherwise it will be returned as 0b.

When writing to this data type, all status bits written with a 1b are cleared. All others remain unchanged. Persistent faults will be immediately re-asserted. In this case <Select> is <RailSel>, and <CmdData> is <AVSBus_Status>. This is the only command in which it is possible to set <Select> to all 1’s for a broadcast read, because the AVSBus Slave simply combines the values of each status bit for all active rails using an AND function, and returns the resulting value, effectively providing a quick overview of the entire device.

8.9

AVSBus Version Read (Command Data Type = 1111b)
This type allows the AVSBus Master to read the version of AVSBus implemented by an AVSBus Slave. For PMBus 1.3, the <AVSBus_Version> value is 0000b. Following the bit justification rule, the 4-bit <AVSBus_Version> field is aligned on the LSB of the <CmdData> field, with all preceding bits filled with zeroes. There is no selector for AVSBus version. <Select> must be set to all 1’s for this command.

8.10

Manufacturer-Specific Read/Write (Group 1b, Data Types 0000b to 1111b)
The definition of <Select> and <CmdData> for each one of these data types is specific to each device. In all other regards, these commands follow the same frame structure and protocol rules that apply to Group 0b data types. The product literature of an AVSBus Slave must clearly identify the manufacturerspecific data types it supports, together with the size of the fields, their encoding and whether they allow Read-only, Write-only or Read/Write commands.

9

Communication From The AVSBus Slave To The AVSBus Master
AVSBus devices will never become bus masters for communication with the host. All transfers are initiated by the master. However, a mechanism for AVSBus Slaves to issue an interrupt to the AVSBus Master is supported so that the slave can send timely status information to the master. Implementation of this mechanism is not mandatory for AVSBus Slaves, although support for the status information (<StatusResponse>) is mandatory for 3-wire mode implementations. See Section 5.3 for more information. When an AVSBus Slave that supports interrupts determines that it needs the AVSBus Master to be aware of any special condition, it can simply signal to the AVSBus Master that it needs a frame to be started. It does this by pulling the AVS_SData line low while the bus is idle. It is up to the AVSBus Master to initiate such frame as soon as practical.

10 PMBus? And AVSBus Device Mapping
Figure 16 shows a hypothetical power management IC. This IC has four controllers that can provide a control signal, typically a pulse width modulated (PWM) signal, to four different power stages. As shown, each power stage generates an output voltage but it is possible that two or more of the power stages could be operated as phases of one interleaved multi-phase power stage. ? 2014 System Management Interface Forum, Inc. All Rights Reserved Page 29 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3
This hypothetical IC also has a PMBus? interface that uses the PAGE command to individually address the four controllers. The IC also has two AVSBus interface ports. AVSBus Port 1 is routed within the power management IC to controllers 2 and 3. This means AVSBus Master 1 is supporting two rails. AVSBus Port 2 is routed only to controller 4. Controller 1 is controlled only through the PMBus and does not have an AVSBus port connection. In order to properly design the power system, the system engineer needs to know which of the controllers (and their PAGE numbers) are controlled only by the PMBus interface and which are controlled by both the PMBus and AVSBus interfaces. There could also be, although not shown in this example, outputs that were controlled only by an AVSBus interface. The information describing the connection of internal elements or controllers or power management ICs or device to externally connected PMBus and AVSBus shall be fully described in the product literature. At this time there is no standard mechanism provided for the details of these connections to be discoverable by either a PMBus system host or an AVSBus master. This capability may be included in a future release of the PMBus and AVSBus standards. Device manufacturers may provide this capability through manufacturer specific commands.

Figure 16. Example Power Management IC With Multiple PAGEs And Multiple AVSBus Ports

11 Accuracy
Each AVSBus device will specify in its product literature the accuracy with which the target voltage and other parameters can be set and reported.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 30 Of 31

PMBus? Power System Mgmt Protocol Specification – Part III – Revision 1.3

12 Summary Of Changes
DISCLAIMER: The section is provided for reference only and for the convenience of the reader. No suggestion, statement or guarantee is made that the description of the changes listed below is sufficient to design a device compliant with this document.

Revision 1.3 is the initial release of Part III of the PMBus specifications. There were no earlier revisions.

? 2014 System Management Interface Forum, Inc. All Rights Reserved

Page 31 Of 31


相关文章:
具备I2C - PMBus 数字电源系统管理和内置 EEPROM 的 同...
具备I2C / PMBus 数字电源系统管理和内置 EEPROM 的 同步降压型 DC/DC 控制器 2012 年 8 月 23 日–凌力尔特公司(Linear Technology Corporation) 推出同步...
电源管理
1.电源管理 2.PMBus电源系统的共通语言 3.功率因数校正之基本原理 4.交错式电源 5.波谷电流回授控制 6.返驰式隔离电源设计 7.为直流电源转换器选择正确的电感...
I2CBus与SMBus间技术差异
系统管理总线(SMBus)控制... 43页 免费 I2C与SMBus的区别 5页 免费 PMBus--数字电源开放标准... 4页 免费 i2c总线协议(中文版pdf) 38页 1下载券 ...
电源管理 IC 以数字方式监视和控制 8 个电源
PMBus 是一种开放式且被广泛采用的标准,它明确定义了用于单独 DC/DC POL 转换器的数字电源管理协议。LTC2978 支持大量的 PMBus 命令。另外,该器件还 具有一些 ...
SMBUS中PEC查表程序(16字节表)
SMBUS中PEC查表程序(16字节表)_信息与通信_工程科技_专业资料。原创,根据HOT大叔的程序改编面来,修正了大叔的BUG并美化SMBUS 中 PEC 查表程序 查表程序(16 ...
MAX15301数据手册中文版
详细描述 MAX15301 是一种创新的,兼容 PMBus 命令,混合信号的电源管理芯片,对数字负载 点来说这种芯片内置一种高性能数字 PWM 控制器。MAX15301 是基于 MAXIM ...
常见数字电源技术及应用
输出电压、输 3 出电流和温度限制等参数的参考值在生产期间被保存在非易失性内存中 ,或者可以通过 PMBus 输入。在系统启动时,数据会由 EEPROM 下载到数据内存中...
ST_STM32L476Gxx系列超低功耗MCU开发方案
(1Mb/s)、SMBus/PMBus 6 个 USART(ISO 7816、LIN、IrDA、调制解调器) 3 个 SPI(4 个 SPI+Quad SPI) CAN(2.0B Active)和 SDMMC 接口 SWPMI 单线协议主...
ST STM32L476Gxx系列超低功耗MCU开发方案
18x communication interfaces – USB OTG 2.0 full-speed, LPM and BCD – 2x SAIs (serial audio interface) – 3x I2C FM+(1 Mbit/s), SMBus/PMBus –...
数据中心建设_图文
同样也提供多种普通及白金级电源选择,还可支持 PMBUS 电源, 完美支持 Intel 最新 DPNM 2.0 技术。 ? 增强的散热系统、更低的功耗表现 特别设计的风流控制系统可...
更多相关标签: